Table 9: Pickup LED
LED state Description
Off Normal operation.
On A protection function has picked up and an indication message is displayed.
If several protection functions pick up within a short time, the last pickup
is indicated on the display.
Flashing
A protection function is blocked.
The blocking indication disappears when the blocking is removed or when
the protection function is reset.
Table 10: Trip LED
LED state Description
Off Normal operation.
On A protection function has tripped and an indication message is displayed.
The trip indication is latching and must be reset via communication or by
pressing
.
If several protection functions trip within a short time, the last trip is
indicated on the display.
Alarm indicators
The 11 matrix programmable LEDs are used for alarm indication.
Table 11: Alarm indications
LED state
Description
Off Normal operation. All activation signals are off.
On Non-latched mode: activation signal is still on.
Latched mode: activation signal is still on, or it is off but has not been
acknowledged.
Latched flashing mode: activation signal is still on but has been
acknowledged.
Flashing
Non-latched flashing mode: activation signal is still on.
Latched flashing mode: activation signal is still on, or it is off but has not
been acknowledged.
1MAC456939-IB D Section 3
620 series overview
620 series ANSI 27
Operation Manual