EasyManua.ls Logo

ABB Relion 620 Series - Section 5 Protection Relay Operation; Normal Operation; Disturbance Identification

ABB Relion 620 Series
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 5 Protection relay operation
5.1 Normal operation
In a normal protection relay use situation, the basic operation includes monitoring and
checking procedures.
Monitoring measured values
Checking object states
Checking function setting parameters
Checking events and alarms
All basic operations can be performed via the LHMI, WHMI or with PCM600.
For more information, see the PCM600 documentation.
5.2 Disturbance identification
Disturbances and their causes can be identified by indicator LEDs: Normal, Pickup and
Trip. During normal operation, the Normal LED is steady green.
Table 17: Disturbance indications
LED
State Description
Pickup LED Yellow, steady Protection picked up
Pickup LED Yellow, flashing Protection function blocked
Trip LED Red, steady Protection tripped
Normal LED Green, flashing Internal fault
Further actions to be taken to identify the disturbance:
1MAC456939-IB D Section 5
Protection relay operation
620 series ANSI 77
Operation Manual

Table of Contents

Other manuals for ABB Relion 620 Series

Related product manuals