16.1.5 Settings
SEMOD130322-4 v6
The available setting parameters of the measurement function (MMXU, MSQI) are depending on
the actual hardware (TRM) and the logic configuration made in PCM600.
These six functions are not handled as a group, so parameter settings are only available in the first
setting group.
The following terms are used in the Unit and Description columns:
VBase: Base voltage in primary kV. This voltage is used as reference for voltage setting. It can
be suitable to set this parameter to the rated primary voltage supervised object.
IBase: Base current in primary A. This current is used as reference for current setting. It can be
suitable to set this parameter to the rated primary current of the supervised object.
SBase: Base setting for power values in MVA.
PID-3584-SETTINGS v6
Table 732: CVMMXN Non group settings (basic)
Name Values (Range) Unit Step Default Description
SLowLim 0.0 - 2000.0 %SB 0.1 80.0 Low limit in % of SBase
SLowLowLim 0.0 - 2000.0 %SB 0.1 60.0 Low Low limit in % of SBase
SMin 0.0 - 2000.0 %SB 0.1 50.0 Minimum value in % of SBase
SMax 0.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
SRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
PMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBase
PMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
PRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
QMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBase
QMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
QRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
PFMin -1.000 - 1.000 - 0.001 -1.000 Minimum value
PFMax -1.000 - 1.000 - 0.001 1.000 Maximum value
PFRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
VMin 0.0 - 200.0 %VB 0.1 50.0 Minimum value in % of VBase
VMax 0.0 - 200.0 %VB 0.1 200.0 Maximum value in % of VBase
VRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
IMin 0.0 - 500.0 %IB 0.1 5.0 Minimum value in % of IBase
Table continues on next page
Section 16 1MRK 502 066-UUS B
Monitoring
1016
Technical manual