Name Values (Range) Unit Step Default Description
VC_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
VC_LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
VC_AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Table 743: VNMMXU Non group settings (advanced)
Name Values (Range) Unit Step Default Description
VA_HiHiLim 0.0 - 200.0 %VB 0.1 150.0 High High limit in % of UBase
VA_HiLim 0.0 - 200.0 %VB 0.1 120.0 High limit in % of VBase
VA_LowLim 0.0 - 200.0 %VB 0.1 80.0 Low limit in % of VBase
VA_LowLowLim 0.0 - 200.0 %VB 0.1 60.0 Low Low limit in % of VBase
VMagComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at
100% of Vn
VA_Min 0.0 - 200.0 %VB 0.1 50.0 Minimum value in % of VBase
VB_HiHiLim 0.0 - 200.0 %VB 0.1 150.0 High High limit in % of UBase
VB_HiLim 0.0 - 200.0 %VB 0.1 120.0 High limit in % of VBase
VB_LowLim 0.0 - 200.0 %VB 0.1 80.0 Low limit in % of VBase
VB_LowLowLim 0.0 - 200.0 %VB 0.1 60.0 Low Low limit in % of VBase
VB_Min 0.0 - 200.0 %VB 0.1 50.0 Minimum value in % of VBase
VC_HiHiLim 0.0 - 200.0 %VB 0.1 150.0 High High limit in % of UBase
VC_HiLim 0.0 - 200.0 %VB 0.1 120.0 High limit in % of VBase
VC_LowLim 0.0 - 200.0 %VB 0.1 80.0 Low limit in % of VBase
VC_LowLowLim 0.0 - 200.0 %VB 0.1 60.0 Low Low limit in % of VBase
VC_Min 0.0 - 200.0 %VB 0.1 50.0 Minimum value in % of VBase
16.1.6 Monitored data
PID-3584-MONITOREDDATA v5
Table 744: CVMMXN Monitored data
Name Type Values (Range) Unit Description
S REAL - MVA Apparent Power magnitude of deadband
value
P REAL - MW Active Power magnitude of deadband
value
Q REAL - MVAr Reactive Power magnitude of deadband
value
PF REAL - - Power Factor magnitude of deadband
value
Table continues on next page
1MRK 502 066-UUS B Section 16
Monitoring
1027
Technical manual