16.9.6 Settings
PID-3553-SETTINGS v5
Table 791: L4UFCNT Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
On
- - Disabled Operation Disabled/Enabled
CountType Positive edge
Negative edge
Both edges
- - Positive edge Select counting on positive and/or
negative sides
CounterLimit1 1 - 65535 - 1 100 Value of the first limit
CounterLimit2 1 - 65535 - 1 200 Value of the second limit
CounterLimit3 1 - 65535 - 1 300 Value of the third limit
CounterLimit4 1 - 65535 - 1 400 Value of the fourth limit
MaxValue 1 - 65535 - 1 500 Maximum count value
OnMaxValue Stop
Rollover Steady
Rollover Pulsed
- - Stop Select if counter stops or rolls over after
reaching maxValue with steady or pulsed
overflow flag
InitialValue 0 - 65535 - 1 0 Initial count value after reset of the
function
16.9.7 Monitored data
PID-3553-MONITOREDDATA v4
Table 792: L4UFCNT Monitored data
Name Type Values (Range) Unit Description
VALUE INTEGER - - Counted value
16.9.8 Technical data
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v2
Table 793: L4UFCNTtechnical data
Function Range or value Accuracy
Counter value 0-65535 -
Max. count up speed 30 pulses/s (50% duty cycle) -
16.10 Running hour-meter TEILGAPC
16.10.1 Identification
GUID-3F9EF4FA-74FA-4D1D-88A0-E948B722B64F v1
Function Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2 device
number
Running hour-meter TEILGAPC - -
Section 16 1MRK 502 066-UUS B
Monitoring
1096
Technical manual