16.10.2 Functionality
GUID-464FB24F-B367-446C-963A-A14841943B87 v2
The Running hour-meter (TEILGAPC) function is a function that accumulates the elapsed time
when a given binary signal has been high, see also figure
571.
Time Accumulation
with Retain
BLOCK
ACC_HOUR
RESET
IN
tWarning
tAlarm
OVERFLOW
WARNING
ALARM
q
-1
a>b
a
b
a>b
a
b
a>b
a
b
&
&
&
q
-1
= unit delay
IEC15000321-1-en.vsd
ACC_DAY
99 999.9 h
tAddToTime
ADDTIME
IEC15000321 V1 EN-US
Figure 571: TEILGAPC logics
The main features of TEILGAPC are:
Applicable to very long time accumulation (≤ 99999.9 hours)
Supervision of limit transgression conditions and rollover/overflow
Possibility to define a warning and alarm with the resolution of 0.1 hours
Retain any saved accumulation value at a restart
Possibilities for blocking and reset
Possibility for manual addition of accumulated time
Reporting of the accumulated time
16.10.3 Function block
GUID-D0E9688B-C9D9-44B7-BD95-81132CCA5E4F v1
TEIL GAPC
BL OCK
IN
ADDTIME
RESET
ALARM
WARNING
OVERFLOW
ACC_HOUR
ACC_DAY
IEC15000323.vsdx
IEC15000323 V1 EN-US
Figure 572: TEILGAPC function block
1MRK 502 066-UUS B Section 16
Monitoring
1097
Technical manual

Table of Contents