Name Type Description
EARACC REAL Accumulated reverse active energy value in Ws
ERFACC REAL Accumulated forward reactive energy value in VArS
ERRACC REAL Accumulated reverse reactive energy value in VArS
MAXPAFD REAL Maximum forward active power demand value for set interval
MAXPARD REAL Maximum reverse active power demand value for set interval
MAXPRFD REAL Maximum forward reactive power demand value for set interval
MAXPRRD REAL Maximum reactive power demand value in reverse direction
17.2.5 Settings
PID-3843-SETTINGS v5
Table 805: ETPMMTR Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
EnaAcc Disabled
Enabled
- - Disabled Activate the accumulation of energy values
tEnergy 1 Minute
5 Minutes
10 Minutes
15 Minutes
30 Minutes
60 Minutes
180 Minutes
- - 1 Minute Time interval for energy calculation
tEnergyOnPls 0.100 - 60.000 s 0.001 1.000 Energy accumulated pulse ON time in secs
tEnergyOffPls 0.100 - 60.000 s 0.001 0.500 Energy accumulated pulse OFF time in
secs
EAFAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active forward
accumulated energy value
EARAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active reverse
accumulated energy value
ERFAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive forward
accumulated energy value
ERRAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive reverse
accumulated energy value