Table 806: ETPMMTR Non group settings (advanced)
Name Values (Range) Unit Step Default Description
EALim 0.001 -
10000000000.00
0
MWh 0.001 1000000.000 Active energy limit
ERLim 0.001 -
10000000000.00
0
MVArh 0.001 1000.000 Reactive energy limit
EnZeroClamp Disabled
Enabled
- - Enabled Enable of zero point clamping detection
function
LevZeroClampP 0.001 - 10000.000 MW 0.001 10.000 Zero point clamping level at active Power
LevZeroClampQ 0.001 - 10000.000 MVAr 0.001 10.000 Zero point clamping level at reactive Power
DirEnergyAct Forward
Reverse
- - Forward Direction of active energy flow Forward/
Reverse
DirEnergyReac Forward
Reverse
- - Forward Direction of reactive energy flow Forward/
Reverse
EAFPrestVal 0.000 -
100000000.000
MWh 0.001 0.000 Preset Initial value for forward active
energy
EARPrestVal 0.000 -
100000000.000
MWh 0.001 0.000 Preset Initial value for reverse active
energy
ERFPresetVal 0.000 -
100000000.000
MVArh 0.001 0.000 Preset Initial value for forward reactive
energy
ERRPresetVal 0.000 -
100000000.000
MVArh 0.001 0.000 Preset Initial value for reverse reactive
energy
17.2.6 Monitored data
PID-3843-MONITOREDDATA v3
Table 807: ETPMMTR Monitored data
Name Type Values (Range) Unit Description
EAFACC REAL - MWh Accumulated forward active energy value
in Ws
EARACC REAL - MWh Accumulated reverse active energy value in
Ws
ERFACC REAL - MVArh Accumulated forward reactive energy
value in VArS
ERRACC REAL - MVArh Accumulated reverse reactive energy value
in VArS
MAXPAFD REAL - MW Maximum forward active power demand
value for set interval
MAXPARD REAL - MW Maximum reverse active power demand
value for set interval
MAXPRFD REAL - MVAr Maximum forward reactive power demand
value for set interval
MAXPRRD REAL - MVAr Maximum reactive power demand value in
reverse direction