18.4.2 Communication interfaces and protocols
GUID-35C845D3-574A-40D1-AEF1-9E0D330E31DE v6
Table 809: Supported station communication interfaces and protocols
Protocol Ethernet Serial
100BASE-FX (ST connector) Glass fiber (ST connector) EIA-485
IEC 61850–8–1 - -
DNP3
IEC 60870-5-103 -
= Supported
When double Ethernet ports are activated, make sure that the two ports are
connected to different subnets. For example: Port 1 has IP-address 138.227.102.10
with subnet mask 255.255.255.0 and port 2 has IP-address 138.227.103.10 with
subnet mask 255.255.255.0
18.4.3 Settings
PID-6495-SETTINGS v3
Table 810: IEC61850-8-1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
PortSelGOOSE Front
LANAB
LANCD
- - LANAB Port selection for GOOSE communication
PortSelMMS Front
LANAB
LANCD
Any
- - Any Port selection for MMS communication
Protocol Edition Ed 1
Ed 2
- - Ed 1 Protocol Edition
RemoteModControl Disabled
Maintenance
All levels
- - Disabled Remote Mode Control
AllowSimulation No
Yes
- - No Allow simulated GOOSE values or
simulated sampled measured values
IEC61850BufTimEnable Disabled
Enabled
- - Enabled Enable BRC buf time behavior
EnableSettings Disabled
Enabled
- - Disabled Enable 61850 Edition 2 setting
ResvTms 1 - 3600 s 1 60 Reservation time
1MRK 502 066-UUS B Section 18
Station communication
1115
Technical manual