Name Values (Range) Unit Step Default Description
MV hLim -5000.00 -
5000.00
xBase 0.01 800.00 High limit multiplied with the base prefix
(multiplication factor)
MV lLim -5000.00 -
5000.00
xBase 0.01 -800.00 Low limit multiplied with the base prefix
(multiplication factor)
MV llLim -5000.00 -
5000.00
xBase 0.01 -900.00 Low Low limit multiplied with the base
prefix (multiplication factor)
MV min -5000.00 -
5000.00
xBase 0.01 -1000.00 Minimum value multiplied with the base
prefix (multiplication factor)
MV max -5000.00 -
5000.00
xBase 0.01 1000.00 Maximum value multiplied with the base
prefix (multiplication factor)
MV dbType Cyclic
Dead band
Int deadband
- - Dead band Reporting type
MV limHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
18.4.6.5 Monitored data
PID-3779-MONITOREDDATA v5
Table 819: MVGAPC Monitored data
Name Type Values (Range) Unit Description
VALUE REAL - - Magnitude of deadband value
RANGE INTEGER 1=High
2=Low
3=High-High
4=Low-Low
0=Normal
- Range
18.4.6.6 Operation principle
SEMOD55936-5 v6
Upon receiving an analog signal at its input, Generic communication function for Measured Value
(MVGAPC) will give the instantaneous value of the signal and the range, as output values. In the
same time, it will send over IEC 61850-8-1 the value, to other IEC 61850 clients in the substation.
18.4.7 IEC 61850-8-1 redundant station bus communication
GUID-FF43A130-7D2D-4BA3-B51C-80398D73228F v2
GUID-00C469E6-00D4-4780-BD0D-426647AB8E0F v3.1.1
Function description LHMI and ACT
identification
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Dual ethernet port
link status
PRPSTATUS PRPSTATUS - -
IEC 62439-3 parallel
redundancy
protocol
PRP PRP - -
Section 18 1MRK 502 066-UUS B
Station communication
1120
Technical manual