18.4.6.1 Functionality
SEMOD55872-5 v9
Generic communication function for Measured Value MVGAPC function is used to send the
instantaneous value of an analog signal to other systems or equipment in the substation. It can
also be used inside the same IED, to attach a RANGE aspect to an analog value and to permit
measurement supervision on that value.
18.4.6.2 Function block
SEMOD54712-4 v4
MVGAPC
BLOCK
^IN
^VALUE
RANGE
IEC14000022-1-en.vsd
IEC14000022 V1 EN-US
Figure 585: MVGAPC function block
18.4.6.3 Signals
SEMOD55948-1 v2
PID-3779-INPUTSIGNALS v5
Table 816: MVGAPC Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN REAL 0 Analog input value
PID-3779-OUTPUTSIGNALS v5
Table 817: MVGAPC Output signals
Name Type Description
VALUE REAL Magnitude of deadband value
RANGE INTEGER Range
18.4.6.4 Settings
SEMOD55954-1 v2
PID-3779-SETTINGS v5
Table 818: MVGAPC Non group settings (basic)
Name Values (Range) Unit Step Default Description
BasePrefix micro
milli
unit
kilo
Mega
Giga
Tera
- - unit Base prefix (multiplication factor)
MV db 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
MV zeroDb 0 - 100000 m% 1 500 Zero point clamping in 0.001% of range
MV hhLim -5000.00 -
5000.00
xBase 0.01 900.00 High High limit multiplied with the base
prefix (multiplication factor)
Table continues on next page
1MRK 502 066-UUS B Section 18
Station communication
1119
Technical manual