18.5.4 Settings
SEMOD166625-1 v2
PID-4052-SETTINGS v5
Table 829: MU1_4I_4U Non group settings (basic)
Name Values (Range) Unit Step Default Description
SVId 10 - 34 - 1 ABB_MU0101 MU identifier
SmplGrp 0 - 65535 - 1 0 Sampling group
CT_WyePoint1 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint2 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint3 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint4 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
Table 830: MU1_4I_4U Non group settings (advanced)
Name Values (Range) Unit Step Default Description
SynchMode NoSynch
Init
Operation
- - Operation Synchronization mode
PID-4053-SETTINGS v5
Table 831: MU2_4I_4U Non group settings (basic)
Name Values (Range) Unit Step Default Description
SVId 10 - 34 - 1 ABB_MU0102 MU identifier
SmplGrp 0 - 65535 - 1 0 Sampling group
CT_WyePoint1 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint2 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint3 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint4 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
Table 832: MU2_4I_4U Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
SynchMode NoSynch
Init
Operation
- - Operation Synchronization mode