PID-4054-SETTINGS v5
Table 833: MU3_4I_4U Non group settings (basic)
Name Values (Range) Unit Step Default Description
SVId 10 - 34 - 1 ABB_MU0103 MU identifier
SmplGrp 0 - 65535 - 1 0 Sampling group
CT_WyePoint1 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint2 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint3 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint4 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
Table 834: MU3_4I_4U Non group settings (advanced)
Name Values (Range) Unit Step Default Description
SynchMode NoSynch
Init
Operation
- - Operation Synchronization mode
PID-4168-SETTINGS v5
Table 835: MU4_4I_4U Non group settings (basic)
Name Values (Range) Unit Step Default Description
SVId 10 - 34 - 1 ABB_MU0104 MU identifier
SmplGrp 0 - 65535 - 1 0 Sampling group
CT_WyePoint1 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint2 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint3 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint4 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
Table 836: MU4_4I_4U Non group settings (advanced)
Name Values (Range) Unit Step Default Description
SynchMode NoSynch
Init
Operation
- - Operation Synchronization mode
Section 18 1MRK 502 066-UUS B
Station communication
1128