EasyManua.ls Logo

ABB Relion 670 series - Page 1135

ABB Relion 670 series
1432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PID-4169-SETTINGS v5
Table 837: MU5_4I_4U Non group settings (basic)
Name Values (Range) Unit Step Default Description
SVId 10 - 34 - 1 ABB_MU0105 MU identifier
SmplGrp 0 - 65535 - 1 0 Sampling group
CT_WyePoint1 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint2 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint3 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint4 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
Table 838: MU5_4I_4U Non group settings (advanced)
Name Values (Range) Unit Step Default Description
SynchMode NoSynch
Init
Operation
- - Operation Synchronization mode
PID-4170-SETTINGS v5
Table 839: MU6_4I_4U Non group settings (basic)
Name Values (Range) Unit Step Default Description
SVId 10 - 34 - 1 ABB_MU0106 MU identifier
SmplGrp 0 - 65535 - 1 0 Sampling group
CT_WyePoint1 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint2 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint3 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CT_WyePoint4 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
Table 840: MU6_4I_4U Non group settings (advanced)
Name Values (Range) Unit Step Default Description
SynchMode NoSynch
Init
Operation
- - Operation Synchronization mode
1MRK 502 066-UUS B Section 18
Station communication
1129
Technical manual

Table of Contents