16 pulse counter value function blocks PCFCNT:1 to PCFCNT:16, and 24 mA input service values
function blocks SMMI1_In1 to 6 – SMMI4_In1 to 6 are available in the IEDs.
The first LON address in every event function block is found in table 850
Table 850: LON adresses for Event functions
Function block First LON address in
function block
EVENT:1 1024
EVENT:2 1040
EVENT:3 1056
EVENT:4 1072
EVENT:5 1088
EVENT:6 1104
EVENT:7 1120
EVENT:8 1136
EVENT:9 1152
EVENT:10 1168
EVENT:11 1184
EVENT:12 1200
EVENT:13 1216
EVENT:14 1232
EVENT:15 1248
EVENT:16 1264
EVENT:17 1280
EVENT:18 1296
EVENT:19 1312
EVENT:20 1328
Event masks
M15083-78 v3
The event mask for each input can be set individually from Parameter Setting Tool (PST) under:
Settings/IED settings/ Monitoring / EventFunction or via parameter setting tool (PST) as
follows:
No events
OnSet, at pick-up of the signal
OnReset, at drop-out of the signal
OnChange, at both pick-up and drop-out of the signal
AutoDetect, event system itself make the reporting decision, (reporting criteria for integers
has no semantic, prefer to be set by the user)
The following type of signals from application functions can be connected to the event function
block.
Single indication
M15083-123 v2
1MRK 502 066-UUS B Section 18
Station communication
1137
Technical manual