Function block SPA address CMD Input SPA address CMD output
SINGLECMD3-Cmd1 4-S-4705 5-O-543
SINGLECMD3-Cmd2 4-S-4706 5-O-544
SINGLECMD3-Cmd3 4-S-4707 5-O-545
SINGLECMD3-Cmd4 4-S-4708 5-O-546
SINGLECMD3-Cmd5 4-S-4709 5-O-547
SINGLECMD3-Cmd6 4-S-4710 5-O-548
SINGLECMD3-Cmd7 4-S-4711 5-O-549
SINGLECMD3-Cmd8 4-S-4712 5-O-550
SINGLECMD3-Cmd9 4-S-4713 5-O-551
SINGLECMD3-Cmd10 4-S-4714 5-O-552
SINGLECMD3-Cmd11 4-S-4715 5-O-553
SINGLECMD3-Cmd12 4-S-4716 5-O-554
SINGLECMD3-Cmd13 4-S-4717 5-O-555
SINGLECMD3-Cmd14 4-S-4718 5-O-556
SINGLECMD3-Cmd15 4-S-4719 5-O-557
SINGLECMD3-Cmd16 4-S-4720 5-O-558
Figure 592 shows an application example of how the user can, in a simplified way, connect the
command function via the configuration logic circuit in a protection IED for control of a circuit
breaker.
A pulse via the binary outputs of the IED normally performs this type of command control. The SPA
addresses to control the outputs OUT1 – OUT16 in SINGLECMD:1 are shown in table
857.
SINGLECMD
BLOCK ^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
^OUT9
^OUT10
^OUT11
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16
AND
INPUT1
INPUT2
INPUT3
INPUT4
OUT
NOUT
PULSETIMER
INPUT OUT
#CD01-CMDOUT1
#CD01-CMDOUT2
#CD01-CMDOUT3
#CD01-CMDOUT4
#CD01-CMDOUT5
#CD01-CMDOUT6
#CD01-CMDOUT7
#CD01-CMDOUT15
#CD01-CMDOUT16
#CD01-CMDOUT8
#CD01-CMDOUT9
#CD01-CMDOUT10
#CD01-CMDOUT11
#CD01-CMDOUT12
#CD01-CMDOUT13
#CD01-CMDOUT14
SYNCH OK
PULSETIMER
INPUT OUT
To output board, CLOSE
To output board, OPEN
IEC05000717-3-en.vsd
IEC05000717 V3 EN-US
Figure 592: Application example showing a simplified logic diagram for control of a circuit
breaker
The MODE input defines if the output signals from SINGLECMD:1 is off, steady or setable pulse
length signals. This is set in Parameter Setting Tool (PST) under: Main Menu/Settings / IED
Settings / Control / Commands / Single Command or via Parameter Setting Tool (PST).
Event function
M11880-82 v4
Event function is intended to send time-tagged events to the station level (for example, operator
workplace) over the station bus. The events are there presented in an event list. The events can be
created from both internal logical signals and binary input channels. All the internal signals are
Section 18 1MRK 502 066-UUS B
Station communication
1158
Technical manual

Table of Contents