18.8.5.4 Signals
PID-3974-INPUTSIGNALS v4
Table 866: I103EF Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
51_EFFW BOOLEAN 0 Information number 51, ground-fault forward
52_EFREV BOOLEAN 0 Information number 52, ground-fault reverse
18.8.5.5 Settings
PID-3974-SETTINGS v4
Table 867: I103EF Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 160 Function type (1-255)
18.8.6 Function status fault protection for IEC 60870-5-103
I103FLTPROT
18.8.6.1 Functionality
GUID-6D52F442-1592-4BA7-919C-0CD79046CAE5 v1
I103FLTPROT is used for fault indications in monitor direction. Each input on the function block is
specific for a certain fault type and therefore must be connected to a correspondent signal
present in the configuration. For example: 68_TRGEN represents the General Trip of the device,
and therefore must be connected to the general trip signal SMPPTRC_TRIP or equivalent.
The delay observed in the protocol is the time difference in between the signal that is triggering
the Disturbance Recorder and the respective configured signal to the IEC 60870-5-103
I103FLTPROT.
18.8.6.2 Identification
GUID-55593EC4-7AED-47A0-8311-DB22D013A193 v1
Function description Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
Function status fault protection for
IEC 60870-5-103
I103FLTPROT - -