18.8.4.4 Signals
PID-3973-INPUTSIGNALS v4
Table 864: I103AR Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
16_ARACT BOOLEAN 0 Information number 16, auto-recloser active
128_CBON BOOLEAN 0 Information number 128, circuit breaker on by auto-recloser
130_BLKD BOOLEAN 0 Information number 130, auto-recloser blocked
18.8.4.5 Settings
PID-3973-SETTINGS v4
Table 865: I103AR Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
18.8.5 Function status ground-fault for IEC 60870-5-103 I103EF
GUID-F23B392E-B55D-4BC3-A0A6-B7992D551092 v1
18.8.5.1 Functionality
GUID-13F90E95-7C8C-4DCB-A9D8-2489B66DB81A v2
I103EF is a function block with defined functions for ground fault indications in monitor direction.
This block includes the
FunctionType
parameter, and the information number parameter is
defined for each output signal.
18.8.5.2 Identification
GUID-033731B7-1B71-4CCC-8356-1C03CBCB23FA v1
Function description Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
Function status earth-fault for IEC
60870-5-103
I103EF - -
18.8.5.3 Function block
GUID-25B47484-2976-4063-BD81-AE02D03B08B0 v1
IEC10000290-1-en.vsd
I103EF
BLOCK
51_EFFW
52_EFREV
IEC10000290 V1 EN-US
Figure 597: I103EF function block
Section 18 1MRK 502 066-UUS B
Station communication
1166
Technical manual