Name Type Default Description
76_TRANS BOOLEAN 0 Information number 76, signal transmitted
77_RECEV BOOLEAN 0 Information number 77, signal received
78_ZONE1 BOOLEAN 0 Information number 78, zone 1
79_ZONE2 BOOLEAN 0 Information number 79, zone 2
80_ZONE3 BOOLEAN 0 Information number 80, zone 3
81_ZONE4 BOOLEAN 0 Information number 81, zone 4
82_ZONE5 BOOLEAN 0 Information number 82, zone 5
84_STGEN BOOLEAN 0 Information number 84, start general
85_BFP BOOLEAN 0 Information number 85, breaker failure
86_MTR_A BOOLEAN 0 Information number 86, trip measuring system phase A
87_MTR_B BOOLEAN 0 Information number 87, trip measuring system phase B
88_MTR_C BOOLEAN 0 Information number 88, trip measuring system phase C
89_MTRN BOOLEAN 0 Information number 89, trip measuring system neutral N
90_IOC BOOLEAN 0 Information number 90, over current trip, stage low
91_IOC BOOLEAN 0 Information number 91, over current trip, stage high
92_IEF BOOLEAN 0 Information number 92, ground-fault trip, stage low
93_IEF BOOLEAN 0 Information number 93, ground-fault trip, stage high
ARINPROG BOOLEAN 0 Autorecloser in progress (SMBRREC- INPROGR)
FLTLOC BOOLEAN 0 Faultlocator faultlocation valid (LMBRFLO-CALCMADE)
18.8.6.5 Settings
PID-3956-SETTINGS v4
Table 869: I103FLTPROT Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 128 Function type (1-255)
18.8.7 IED status for IEC 60870-5-103 I103IED
18.8.7.1 Functionality
GUID-52AC7D0F-33C5-46FC-983E-5CB4B3517D88 v1
I103IED is a function block with defined IED functions in monitor direction. This block uses
parameter as
FunctionType
, and information number parameter is defined for each input signal.
18.8.7.2 Identification
GUID-5EEBE11C-C8E3-4A8A-814F-840E137DB5B5 v1
Function description
Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
IED status for IEC 60870-5-103 I103IED - -
1MRK 502 066-UUS B Section 18
Station communication
1169
Technical manual