Name Type Default Description
INPUT7 BOOLEAN 0 Binary signal input 7
INPUT8 BOOLEAN 0 Binary signal input 8
RT_START BOOLEAN 0 Trig to set base of relative time
GUID-9E29DE39-EA74-4D62-A2BA-F8E31A3D8757 v1
RT_START registers the positive transition (0->1) of a pulse and sets the time from which relative
time is derived. Relative time is assigned only to inputs where the corresponding TypNo
parameter is set to
Relative
. The maximum relative time and unit conform to the IEC60870-5-103
standard.
18.8.9.5 Settings
PID-6485-SETTINGS v4
Table 875: I103USRDEF Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 5 Function type (1-255)
InfNo1 1 - 255 - 1 1 Information number for binary input 1
(1-255)
InfNo2 1 - 255 - 1 2 Information number for binary input 2
(1-255)
InfNo3 1 - 255 - 1 3 Information number for binary input 3
(1-255)
InfNo4 1 - 255 - 1 4 Information number for binary input 4
(1-255)
InfNo5 1 - 255 - 1 5 Information number for binary input 5
(1-255)
InfNo6 1 - 255 - 1 6 Information number for binary input 6
(1-255)
InfNo7 1 - 255 - 1 7 Information number for binary input 7
(1-255)
InfNo8 1 - 255 - 1 8 Information number for binary input 8
(1-255)
TypNo1 Absolute
Relative
- - Absolute Type identification (TYP)
TypNo2 Absolute
Relative
- - Absolute Type identification (TYP)
TypNo3 Absolute
Relative
- - Absolute Type identification (TYP)
TypNo4 Absolute
Relative
- - Absolute Type identification (TYP)
TypNo5 Absolute
Relative
- - Absolute Type identification (TYP)
TypNo6 Absolute
Relative
- - Absolute Type identification (TYP)
TypNo7 Absolute
Relative
- - Absolute Type identification (TYP)
Table continues on next page
1MRK 502 066-UUS B Section 18
Station communication
1173
Technical manual