18.8.10.3 Function block
GUID-C0680812-C488-4546-AA65-F590955DBF0C v1
IEC10000282-1-en.vsd
I103CMD
BLOCK 16-AR
17-DIFF
18-PROT
IEC10000282 V1 EN-US
Figure 602: I103CMD function block
18.8.10.4 Signals
PID-3969-INPUTSIGNALS v4
Table 876: I103CMD Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of commands
PID-3969-OUTPUTSIGNALS v4
Table 877: I103CMD Output signals
Name Type Description
16-AR BOOLEAN Information number 16 disable/enable autorecloser
17-DIFF BOOLEAN Information number 17, block of differential protection
18-PROT BOOLEAN Information number 18, block of protection
18.8.10.5 Settings
PID-3969-SETTINGS v4
Table 878: I103CMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
18.8.11 IED commands for IEC 60870-5-103 I103IEDCMD
18.8.11.1 Functionality
GUID-19AD44B2-21D6-4DB0-AD74-1578DA30C100 v5
I103IEDCMD is a command block in control direction with defined IED functions. All outputs are
pulsed and they are NOT stored. Pulse length is fixed to 400ms.
18.8.11.2 Identification
GUID-0D0B2477-1B0C-48F3-B047-CCF9C7A71856 v1
Function description
Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
IED commands for IEC 60870-5-103 I103IEDCMD - -
1MRK 502 066-UUS B Section 18
Station communication
1175
Technical manual