18.8.11.3 Function block
GUID-52D27CDA-8805-48FA-99BE-2E05A438B0C7 v1
IEC10000283-1-en.vsd
I103IEDCMD
BLOCK 19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4
IEC10000283 V1 EN-US
Figure 603: I103IEDCMD function block
18.8.11.4 Signals
PID-3788-INPUTSIGNALS v4
Table 879: I103IEDCMD Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of commands
PID-3788-OUTPUTSIGNALS v4
Table 880: I103IEDCMD Output signals
Name Type Description
19-LEDRS BOOLEAN Information number 19, reset LEDs
23-GRP1 BOOLEAN Information number 23, activate setting group 1
24-GRP2 BOOLEAN Information number 24, activate setting group 2
25-GRP3 BOOLEAN Information number 25, activate setting group 3
26-GRP4 BOOLEAN Information number 26, activate setting group 4
18.8.11.5 Settings
PID-3788-SETTINGS v4
Table 881: I103IEDCMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 255 Function type (1-255)
18.8.12 Function commands user defined for IEC 60870-5-103
I103USRCMD
18.8.12.1 Functionality
GUID-2989EAC8-20BE-46EE-93FE-C70188D0BC89 v1
I103USRCMD is a command block in control direction with user defined output signals. These
function blocks include the
FunctionType
parameter for each block in the private range, and the
Information number parameter for each output signal.
Section 18 1MRK 502 066-UUS B
Station communication
1176
Technical manual