Name Type Description
APP11_OP BOOLEAN Apparatus 11 position is open
APP11_CL BOOLEAN Apparatus 11 position is closed
APP11VAL BOOLEAN Apparatus 11 position is valid
APP12_OP BOOLEAN Apparatus 12 position is open
APP12_CL BOOLEAN Apparatus 12 position is closed
APP12VAL BOOLEAN Apparatus 12 position is valid
APP13_OP BOOLEAN Apparatus 13 position is open
APP13_CL BOOLEAN Apparatus 13 position is closed
APP13VAL BOOLEAN Apparatus 13 position is valid
APP14_OP BOOLEAN Apparatus 14 position is open
APP14_CL BOOLEAN Apparatus 14 position is closed
APP14VAL BOOLEAN Apparatus 14 position is valid
APP15_OP BOOLEAN Apparatus 15 position is open
APP15_CL BOOLEAN Apparatus 15 position is closed
APP15VAL BOOLEAN Apparatus 15 position is valid
COMMVALID BOOLEAN Communication Valid
TEST BOOLEAN Test Output
18.9.4 Settings
SEMOD173207-1 v2
PID-3784-SETTINGS v4
Table 906: GOOSEINTLKRCV Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
18.9.5 Operation principle
GUID-7275CFBA-F1FE-496A-A9A1-724139DB2081 v1
The APPxVAL output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure condition
and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
Data Value Data Valid Comm Valid Test
Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData 0 0 1 0
Incoming data with q=Invalid 0 0 1 0
Incoming data with q=test 0 0 1 1
Incoming data with q=test+oldData 0 0 1 1