PID-2529-OUTPUTSIGNALS v18
Table 914: GOOSEINTRCV Output signals
Name Type Description
INTOUT INTEGER Integer output
DATAVALID BOOLEAN Data valid for integer output
COMMVALID BOOLEAN Communication valid for integer output
TEST BOOLEAN Test output
18.12.5 Settings
PID-2529-SETTINGS v18
Table 915: GOOSEINTRCV Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
18.12.6 Operation principle
GUID-5BBDF772-3B3E-4F7C-ABE9-18CE3C1A2E2D v2
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure condition
and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of a cross to receive
the integer values.
The implementation for IEC61850 quality data handling is restricted to a simple
level. If quality data validity is GOOD then the DATAVALID output will be HIGH. If
quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA
then the DATAVALID output will be LOW.
18.13 GOOSE function block to receive a measurand value
GOOSEMVRCV
18.13.1 Identification
GUID-B1FFBE08-C823-4A58-9FE0-A9A20DA6BB44 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive a
measurand value
GOOSEMVRCV - -
1MRK 502 066-UUS B Section 18
Station communication
1201
Technical manual