ABB Relion 670 series - Page 320

ABB Relion 670 series
1432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
K
Z Z
Z
N
set set
set
=
0 1
3 1
IECEQUATION15017 V1 EN-US
Z R Zx j X Zx
set
0 0 0= +
IECEQUATION15018 V1 EN-US
For Zone 1,
Z R PEZ j X PEZ
set
1 1 1 1 1= +
IECEQUATION15019 V1 EN-US
For Zone 2-5 and RV,
Z R Zx j X Zx
set
1 1 1= +
IECEQUATION15020 V1 EN-US (Equation 90)
where
Z set0
is the complex zero sequence impedance of the line in Ω/phase
Z set1
is the complex positive sequence impedance of the line in Ω/
phase
R1PEZ1
is the positive sequence resistive reach of the line in Ω/phase
for phase-to-ground fault for zone 1
X1PEZ1
is the positive sequence reactance reach of the line in Ω/phase
for phase-to-ground fault for zone 1
R0Zx
is the zero sequence resistive reach of the line in Ω/phase for
zone x (x=2-5, or RV)
X0Zx
is the zero sequence reactance reach of the line in Ω/phase for
zone x (x=2-5, or RV)
For an earth fault in phase A, the angle β between the compensation voltage and the polarizing
voltage
Vpol
is,
β
= + arg[ ( ) ] ( )V I I K Z V
A A N set pol
3 0 1 arg
ANSIEQUATION15021 V1 EN-US (Equation 91)
where
VA
is the phase voltage in faulty phase A
IA
is the phase current in faulty phase A
3I
0
is the zero-sequence current in faulty phase A
Z set1
is the complex positive sequence impedance of the line in Ω/
phase for phase-to-ground fault in zone direction
Vpol
is the polarizing voltage for phase A
Section 7 1MRK 502 066-UUS B
Impedance protection
314
Technical manual