The calculated
R
calc
and
X
calc
are compared with the non-directional phase-to-phase quadrilateral
characteristics defined by the reactance reaches (
X1FwPPZx
and
X1RvPPZx
, where
x
= 1 to 5 or RV),
resistance reaches (
R1FwPPZx
, where
x
= 1 to 5 or RV) for the zones, as well as the fault resistance
reach setting for phase-to-phase loops ((
RFPPZx
, where
x
= 1, 2 or RV), (
RFFwPPZx
and
RFRvPPZx
,
where
x
= 3 to 5 or RV)), as shown in Figure 174. If is inside the non-directional phase-to-phase
characteristic, the STNDZx output is set to TRUE.
For phase-to-ground faults (Figure 175, upper part), the ground return compensation applies
according to Equation 98 (example for a phase L1 to ground fault).
11 0
31
LLN F
UIKIpZIRF
IECEQUATION18007 V1 EN-US (Equation 98)
Where,
p
is the fault location and
RF
is the calculated fault resistance.
p
and
RF
are unknown and needs to
be solved.
is the zero-sequence current.
is the ground compensation factor and it is defined as:
R FwPEZx j X FwPEZx
IECEQUATION18020 V1 EN-US
Where,
is the set complex zero sequence impedance of the line in Ω/phase.
is the set complex positive sequence impedance of the line in Ω/phase.
R1FwPEZx
is the positive sequence resistive reach of the line in Ω/phase for phase-to-ground fault
in zone direction for zone
x
(
x
= 1 to 5 or RV).
X1FwPEZx
is the positive sequence reactance reach of the line in Ω/phase for phase-to-ground
fault in zone direction for zone
x
(
x
= 1 to 5 or RV).
R0FwPEZx
is the zero sequence resistive reach of the line in Ω/phase for phase-to-ground fault in
zone direction for zone
x
(
x
= 1 to 5 or RV).
X0FwPEZx
is the zero sequence reactance reach of the line in Ω/phase for phase-to-ground fault in
zone direction for zone
x
(
x
= 1 to 5 or RV).
is the fault current. It is chosen among phase, zero or negative sequence currents automatically
by the built-in adaptive load compensation algorithm.
The calculated impedances from the relay to the fault
can be represented as:
IECEQUATION18021 V1 EN-US
1MRK 502 066-UUS B Section 7
Impedance protection
345
Technical manual