EasyManua.ls Logo

ABB Relion 670 series - Page 351

ABB Relion 670 series
1432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The calculated
R
calc
and
X
calc
are compared with the non-directional phase-to-phase quadrilateral
characteristics defined by the reactance reaches (
X1FwPPZx
and
X1RvPPZx
, where
x
= 1 to 5 or RV),
resistance reaches (
R1FwPPZx
, where
x
= 1 to 5 or RV) for the zones, as well as the fault resistance
reach setting for phase-to-phase loops ((
RFPPZx
, where
x
= 1, 2 or RV), (
RFFwPPZx
and
RFRvPPZx
,
where
x
= 3 to 5 or RV)), as shown in Figure 174. If is inside the non-directional phase-to-phase
characteristic, the STNDZx output is set to TRUE.
For phase-to-ground faults (Figure 175, upper part), the ground return compensation applies
according to Equation 98 (example for a phase L1 to ground fault).
11 0
31
LLN F
UIKIpZIRF
IECEQUATION18007 V1 EN-US (Equation 98)
Where,
p
is the fault location and
RF
is the calculated fault resistance.
p
and
RF
are unknown and needs to
be solved.
is the zero-sequence current.
is the ground compensation factor and it is defined as:
01
31
00 0
11 1
N
ZZ
K
Z
Z
R FwPEZx j X FwPEZx
Z
R FwPEZx j X FwPEZx


IECEQUATION18020 V1 EN-US
Where,
is the set complex zero sequence impedance of the line in Ω/phase.
is the set complex positive sequence impedance of the line in Ω/phase.
R1FwPEZx
is the positive sequence resistive reach of the line in Ω/phase for phase-to-ground fault
in zone direction for zone
x
(
x
= 1 to 5 or RV).
X1FwPEZx
is the positive sequence reactance reach of the line in Ω/phase for phase-to-ground
fault in zone direction for zone
x
(
x
= 1 to 5 or RV).
R0FwPEZx
is the zero sequence resistive reach of the line in Ω/phase for phase-to-ground fault in
zone direction for zone
x
(
x
= 1 to 5 or RV).
X0FwPEZx
is the zero sequence reactance reach of the line in Ω/phase for phase-to-ground fault in
zone direction for zone
x
(
x
= 1 to 5 or RV).
is the fault current. It is chosen among phase, zero or negative sequence currents automatically
by the built-in adaptive load compensation algorithm.
The calculated impedances from the relay to the fault

calc calc calc
Z
RjX
can be represented as:
1
1
calc
calc
X p X FwPEZx
R
p R FwPEZx RF


IECEQUATION18021 V1 EN-US
1MRK 502 066-UUS B Section 7
Impedance protection
345
Technical manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals