AB
V
12
1
L L set
IZ
1
comp AB AB set
V V I Z
pol
V
AB
I jX
AB
IR
ANSI15000060-1-en.vsdx
ANSI15000060 V1 EN-US
Figure 178: Simplified mho characteristic and vector diagram for phase A-to-B fault
Offset Mho
GUID-2E84AD28-CA5F-4D19-B189-57354C8F7CF9 v1
The characteristic for offset mho is a circle where two points on the circle are given by the two
vectors
Z set1
and
Z RVset1
where
Z set1
and
Z RVset1
are settable through the resistance and
reactance settings in forward and reverse directions.
The condition for operation at phase-to-phase fault is that the angle β between the two
compensated voltages is greater than or equal to 90° (figure
179). The angle will be 90° for fault
location on the boundary of the circle.
The angle β for A to B fault can be defined according to equation 102.
arg
β
=
( )
V I Z
V I Z
AB AB set
AB AB RVset
1
1
ANSIEQUATION15008 V1 EN-US (Equation 102)
where
Z RVset1
is the positive sequence impedance setting for phase-to-phase
fault opposite to zone direction and is defined as
Z R RvPPZx j X RvPPZx
RVset
1 1 1= +
IECEQUATION15013 V1 EN-US (Equation 103)
Section 7 1MRK 502 066-UUS B
Impedance protection
352
Technical manual