Figure 178: Simplified mho characteristic and vector diagram for phase A-to-B fault
Offset Mho
GUID-2E84AD28-CA5F-4D19-B189-57354C8F7CF9 v1
The characteristic for offset mho is a circle where two points on the circle are given by the two
vectors
and
where
and
are settable through the resistance and
reactance settings in forward and reverse directions.
The condition for operation at phase-to-phase fault is that the angle β between the two
compensated voltages is greater than or equal to 90° (figure
179). The angle will be 90° for fault
location on the boundary of the circle.
The angle β for A to B fault can be defined according to equation 102.
arg
β
=
− ⋅
− − ⋅
( )
V I Z
V I Z
AB AB set
AB AB RVset
1
1
ANSIEQUATION15008 V1 EN-US (Equation 102)
where
is the positive sequence impedance setting for phase-to-phase
fault opposite to zone direction and is defined as
Z R RvPPZx j X RvPPZx
RVset
1 1 1= + ⋅
IECEQUATION15013 V1 EN-US (Equation 103)