Comparator
ZAB
<
Comparator
ZBC
<
Comparator
ZCA
<
Timer Logic
tOpDelayZ1
opModetZ1
tripZone1
BLOCK
BLKZ
EnableZone1
EnableZone1
EnableZone1
V3P
I3P
pickupZone1
Z1Fw
Z1Rev
Z1Fw
Z1Rev
Z1Fw
Z1Rev
ANSI11000297_1.en.vsd
OR
ANSI11000297 V1 EN-US
Figure 237: Block diagram of zone 1
The functionality included in zone 1:
Comparator to detect, if the operating impedance has entered inside zone 1 offset mho
characteristic.
All three phase-to-phase loops are implemented separately.
Forward and reverse reach values are provided in percentage of impedance base value at
generator.
Trip time delay is provided.
Comparator characteristics
The comparator consists of offset mho characteristics. Three individual comparators are provided
in the three phase-to-phase loops. The offset mho characteristic is as shown in figure
238.