Name Values (Range) Unit Step Default Description
IntBlkStVal2 1 - 50 %VB 1 20 Voltage setting for internal blocking in %
of VBase, step 2
tBlkUV2 0.000 - 60.000 s 0.001 0.000 Time delay of internal (low level) blocking
for step 2
HystAbs2 0.0 - 50.0 %VB 0.1 0.5 Absolute hysteresis in % of VBase, step 2
Table 336: UV2PTUV (27) Group settings (advanced)
Name Values (Range) Unit Step Default Description
tReset1 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite Time
curve step 1
ResetTypeCrv1 Instantaneous
Frozen timer
Linearly
decreased
- - Instantaneous Selection of used IDMT reset curve type for
step 1
tIReset1 0.000 - 60.000 s 0.001 0.025 Time delay in Inverse-Time reset (s), step 1
ACrv1 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 1
BCrv1 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 1
CCrv1 0.0 - 1.0 - 0.1 0.0 Parameter C for customer programmable
curve for step 1
DCrv1 0.000 - 60.000 - 0.001 0.000 Parameter D for customer programmable
curve for step 1
PCrv1 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 1
CrvSat1 0 - 100 % 1 0 Tuning param for prog. under voltage
Inverse-Time curve, step 1
tReset2 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite Time
curve step 2
ResetTypeCrv2 Instantaneous
Frozen timer
Linearly
decreased
- - Instantaneous Selection of Time Delay reset curve for
step 2
tIReset2 0.000 - 60.000 s 0.001 0.025 Time delay in Inverse-Time reset (s), step 2
ACrv2 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 2
BCrv2 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 2
CCrv2 0.0 - 1.0 - 0.1 0.0 Parameter C for customer programmable
curve for step 2
DCrv2 0.000 - 60.000 - 0.001 0.000 Parameter D for customer programmable
curve for step 2
PCrv2 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 2
CrvSat2 0 - 100 % 1 0 Tuning param for prog. under voltage
Inverse-Time curve, step 2