EasyManua.ls Logo

ABB Relion 670 series - Page 663

ABB Relion 670 series
1432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
neutral point (V
3N
) will be close to zero in case of a stator ground-fault close to the neutral. This
fact alone can be used as an indication of stator ground-fault. To enable better sensitivity and
stability also measurement of the generator's 3
rd
harmonic voltage V
3T
is also used. In addition to
the decrease of V
3N
the generator voltage V
3T
will increase under the stator ground-fault close to
the generator neutral point. Therefore the 3
rd
harmonic voltage V
3T
, (which is a zero sequence
voltage) is used by the protection. In the 3
rd
harmonic voltage differential protection algorithm
equation 198 is used:
3T 3N
3N
V V VBeta+ ³
EQUATION2359-ANSI V1 EN-US (Equation 198)
V
3N
, and V
3T
are third harmonic phasors with real and imaginary parts. The factor
Beta
must be set
not to risk operation under non-faulted conditions.
The voltage V
3N
is measured via a voltage transformer between the generator neutral point and
ground. The voltage V
3T
can be measured in different ways. The setting
TVoltType
defines how the
protection function is fed from voltage transformers at the high voltage side of the generator. If
V
3T
is lower than the set level
VT3BlkLevel
, STEFPHIZ (59THD) function is blocked. The choices of
TVoltType
are:
NoVoltage
: There is no voltage measured from the generator terminal side. This can be the case
when there are only phase-to-phase voltage transformers available at the generator terminal side.
In this case the protection will operate as a simple neutral point 3
rd
harmonic undervoltage
protection, which must be blocked externally during generator start-up and shut-down.
ResidualVoltage
: The function is fed from a broken delta connection of the phase to ground
connected voltage transformers at the generator terminal side, V
3T
=(1/3)*V_Broken_Delta.
AllThreePhases
: The function is fed from the three phase to ground connected voltage
transformers at the generator terminal side. The 3
rd
harmonic voltage V
3T
is calculated in the IED,
V
3T
=(1/3)*(V3A+V3B+V3C).
PhaseA
,
PhaseB
, or
PhaseC
: The function is fed from one phase voltage transformer only. The 3
rd
harmonic zero sequence voltage is assumed to be equal to any of the phase voltages, as the third
harmonic voltage is of zero sequence type, V
3T
=V3Lx.
A simplified block diagram describing the stator ground fault protection function shown in
figure
356.
1MRK 502 066-UUS B Section 9
Voltage protection
657
Technical manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals