V=-3V0
Ipickup
Operate region
I=3Io
mta line
RCADir
ROADir
en05000252_anis.vsd
IEC05000252-ANIS V1 EN-US
Figure 371: I & V directional operating principle for CVGAPC function
where:
RCADir
is 75°
ROADir
is 50°
The second principle, referred to as "
IcosPhi&V
" in the parameter setting tool, checks that:
that the product I·cos(Φ) is bigger than the set pick-up level, where Φ is angle between the
current phasor and the mta line
that the phasor of the measured current is within the operating region (defined by the
I·cos(Φ) straight line and the relay trip angle,
ROADir
parameter setting; see figure 371).
V=-3V0
Operate region
RCADir
ROADir
Ipickup
I=3Io
mta line
F
en05000253_ansi.vsd
ANSI05000253 V1 EN-US
Figure 372: CVGAPC, IcosPhi&V directional operating principle
where:
RCADir
is 75°
ROADir
is 50°
Section 11 1MRK 502 066-UUS B
Multipurpose protection
702
Technical manual