RESIN2
EXCH_IN
BAY_ACK
BAY_VAL
BAY_RES
ACK_F_B
ANY_ACK
VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT
IEC09000807_1_en.vsd
IEC09000807 V1 EN-US
Figure 458: RESIN2 function block
14.3.11.3 Signals
PID-3629-INPUTSIGNALS v4
Table 504: RESIN1 Input signals
Name Type Default Description
BAY_ACK BOOLEAN 0 Another bay has acknowledged the reservation request from this
bay
BAY_VAL BOOLEAN 0 The reservervation and acknowledge signals from another bay are
valid
BAY_RES BOOLEAN 0 Request from other bay to reserve this bay
PID-3629-OUTPUTSIGNALS v4
Table 505: RESIN1 Output signals
Name Type Description
ACK_F_B BOOLEAN All other bays have acknowledged the reservation request from
this bay
ANY_ACK BOOLEAN Any other bay has acknowledged the reservation request from
this bay
VALID_TX BOOLEAN The reservation and acknowledge signals from other bays are
valid
RE_RQ_B BOOLEAN Request from other bay to reserve this bay
V_RE_RQ BOOLEAN Check if the request of reserving this bay is valid
EXCH_OUT INTEGER Used for exchange signals between different ResIn blocks
PID-3630-INPUTSIGNALS v4
Table 506: RESIN2 Input signals
Name Type Default Description
EXCH_IN INTEGER 5 Used for exchange signals between different ResIn blocks
BAY_ACK BOOLEAN 0 Another bay has acknowledged the reservation request from this
bay
BAY_VAL BOOLEAN 0 The reservervation and acknowledge signals from another bay are
valid
BAY_RES BOOLEAN 0 Request from other bay to reserve this bay
1MRK 502 066-UUS B Section 14
Control
865
Technical manual