Name Values (Range) Unit Step Default Description
OperationAdapt Disabled
Enabled
- - Disabled Enable adapt mode
MFMode Follow Cmd
Follow Tap
- - Follow Cmd Select follow tap or follow command
CircCurrBk Alarm
Auto Block
Auto&Man Block
- - Alarm Alarm, auto block or auto&man block for
high circ current
CmdErrBk Alarm
Auto Block
Auto&Man Block
- - Auto Block Alarm, auto block or auto&man block for
command error
OCBk Alarm
Auto Block
Auto&Man Block
- - Auto&Man Block Alarm, auto block or auto&man block for
overcurrent
MFPosDiffBk Alarm
Auto Block
- - Auto Block Alarm or auto block for tap position
difference in MF
OVPartBk Alarm
Auto&Man Block
- - Auto&Man Block Alarm or auto&man partial block for
overvoltage
RevActPartBk Alarm
Auto Block
- - Alarm Alarm or auto partial block for reverse
action
TapChgBk Alarm
Auto Block
Auto&Man Block
- - Auto Block Alarm, auto block or auto&man block for
tap changer error
TapPosBk Alarm
Auto Block
Auto&Man Block
- - Auto Block Alarm, auto or auto&man block for pos sup
UVBk Alarm
Auto Block
Auto&Man Block
- - Auto Block Alarm, auto block or auto&man block for
undervoltage
UVPartBk Alarm
Auto&Man Block
- - Alarm Alarm or auto&man partial block for
undervoltage
GlobalBaseSel1 1 - 12 - 1 1 Selection of one of the Global Base Value
groups, winding 1
GlobalBaseSel2 1 - 12 - 1 1 Selection of one of the Global Base Value
groups, winding 2
PID-6506-SETTINGS v5
Table 535: TCMYLTC Non group settings (basic)
Name Values (Range) Unit Step Default Description
LowVoltTap 1 - 63 - 1 1 Tap position for lowest voltage
HighVoltTap 1 - 63 - 1 33 Tap position for highest voltage
mALow 0.000 - 25.000 mA 0.001 4.000 mA for lowest voltage tap position
mAHigh 0.000 - 25.000 mA 0.001 20.000 mA for highest voltage tap position
CodeType BIN
BCD
Gray
SINGLE
mA
- - BIN Type of code conversion
Table continues on next page
1MRK 502 066-UUS B Section 14
Control
901