14.7 Generic communication function for Double Point
indication DPGAPC
SEMOD55384-1 v4
14.7.1 Identification
GUID-E16EA78F-6DF9-4B37-A92D-5C09827E2297 v3
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Generic communication function for
Double Point indication
DPGAPC - -
14.7.2 Functionality
SEMOD55850-5 v7
Generic communication function for Double Point indication (DPGAPC) function block is used to
send double point position indications to other systems, equipment or functions in the substation
through IEC 61850-8-1 or other communication protocols. It is especially intended to be used in
the interlocking station-wide logics.
14.7.3 Function block
SEMOD54710-4 v5
IEC13000081 V1 EN-US
Figure 477: DPGAPC function block
14.7.4 Signals
SEMOD55883-1 v2
PID-4139-INPUTSIGNALS v12
Table 552: DPGAPC Input signals
Name Type Default Description
OPEN BOOLEAN 0 Open indication
CLOSE BOOLEAN 0 Close indication
VALID BOOLEAN 0 Valid indication
PID-4139-OUTPUTSIGNALS v11
Table 553: DPGAPC Output signals
Name
Type Description
POSITION INTEGER Double point indication
1MRK 502 066-UUS B Section 14
Control
913
Technical manual