14.7.5 Settings
ABBD8E283863 v3
The function does not have any parameters available in the local HMI or PCM600.
14.7.6 Operation principle
SEMOD55861-5 v7
When receiving the input signals, DPGAPC sends the signals over IEC 61850-8-1 to the systems,
equipment or functions that requests and thus subscribes on these signals. To be able to get the
signals into other systems, equipment or functions, one must use other tools, described in the
Engineering manual, and define which function block in which systems, equipment or functions
should receive this information.
More specifically, DPGAPC function reports a combined double point position indication output
POSITION, by evaluating the value and the timestamp attributes of the inputs OPEN and CLOSE,
together with the logical input signal VALID.
When the input signal VALID is active, the values of the OPEN and CLOSE inputs determine the
two-bit integer value of the output POSITION. The timestamp of the output POSITION will have the
latest updated timestamp of the inputs OPEN and CLOSE.
When the input signal VALID is inactive, DPGAPC function forces the position to intermediated
state.
When the value of the input signal VALID changes, the timestamp of the output POSITION will be
updated as the time when DPGAPC function detects the change.
Refer to Table
554 for the description of the input-output relationship in terms of the value and
the quality attributes.
Table 554: Description of the input-output relationship
VALID OPEN CLOSE
POSITION
Value Description
0 - - 0 Intermediate
1 0 0 0 Intermediate
1 1 0 1 Open
1 0 1 2 Closed
1 1 1 3 Bad State
14.8 Single point generic control 8 signals SPC8GAPC
SEMOD176448-1 v3
14.8.1 Identification
SEMOD176456-2 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Single point generic control 8 signals SPC8GAPC - -
Section 14 1MRK 502 066-UUS B
Control
914
Technical manual