Name Values (Range) Unit Step Default Description
UREvClassMask Disabled
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3
- - Disabled Unsolicited response, event class mask
UROfflineRetry 0 - 10 - 1 5 Unsolicited response retries before off-line
retry mode
tVRRetryDelay 0.00 - 60.00 s 0.01 5.00 Unsolicited response retry delay in s
tVROfflRtryDel 0.00 - 60.00 s 0.01 30.00 Unsolicited response off-line retry delay in
s
UREvCntThold1 1 - 100 - 1 5 Unsolicited response class 1 event count
report treshold
tVREvBufTout1 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 1 event buffer
timeout
UREvCntThold2 1 - 100 - 1 5 Unsolicited response class 2 event count
report treshold
tVREvBufTout2 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 2 event buffer
timeout
UREvCntThold3 1 - 100 - 1 5 Unsolicited response class 3 event count
report treshold
tVREvBufTout3 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 3 event buffer
timeout
DelOldBufFull No
Yes
- - No Delete oldest event when buffer is full
ExtTimeFormat LocalTime
UTC
- - UTC External time format
DNPToSetTime No
Yes
- - No Allow DNP to set time in IED
tSynchTimeout 30 - 3600 s 1 1800 Time synch timeout before error status is
generated
TSyncReqAfTout No
Yes
- - No Time synchronization request after
timeout
Averag3TimeReq No
Yes
- - No Use average of 3 time requests
PairedPoint No
Yes
- - Yes Enable paired point
tSelectTimeout 1.0 - 60.0 s 0.1 30.0 Select timeout
tBrokenConTout 0 - 3600 s 1 0 Broken connection timeout
tKeepAliveT 0 - 3600 s 1 10 Keep-Alive timer
14.9.6 Operation principle
SEMOD158597-4 v5
AutomationBits function (AUTOBITS) has 32 individual outputs which each can be mapped as a
Binary Output point in DNP3. The output is operated by a "Object 12" in DNP3. This object contains
parameters for control-code, count, on-time and off-time. To operate an AUTOBITS output point,
1MRK 502 066-UUS B Section 14
Control
933
Technical manual