send a control-code of latch-On, latch-Off, pulse-On, pulse-Off, Trip or Close. The remaining
parameters will be regarded were appropriate. ex: pulse-On, on-time=100, off-time=300, count=5
would give 5 positive 100 ms pulses, 300 ms apart.
There is a BLOCK input signal, which will disable the operation of the function, in the same way the
setting
Operation
:
Enabled/Disabled
does. That means that, upon activation of the BLOCK input,
all 32 CMDBITxx outputs will be set to 0. The BLOCK acts like an overriding, the function still
receives data from the DNP3 master. Upon deactivation of BLOCK, all the 32 CMDBITxx outputs
will be set by the DNP3 master again, momentarily. For AUTOBITS , the PSTO input determines the
operator place. The command can be written to the block while in “Remote”. If PSTO is in “Local”
then no change is applied to the outputs.
14.10 Single command, 16 signals SINGLECMD
SEMOD119849-1 v2
14.10.1 Identification
GUID-2217CCC2-5581-407F-A4BC-266CD6808984 v1
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Single command, 16 signals SINGLECMD - -
14.10.2 Functionality
M12446-6 v5
The IEDs can receive commands either from a substation automation system or from the local
HMI. The command function block has outputs that can be used, for example, to control high
voltage apparatuses or for other user defined functionality.
14.10.3 Function block
SEMOD116040-4 v2
IEC05000698-2-en.vsd
SINGLECMD
BLOCK ^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
^OUT9
^OUT10
^OUT11
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16
IEC05000698 V3 EN-US
Figure 480: SINGLECMD function block
Section 14 1MRK 502 066-UUS B
Control
934
Technical manual