14.10.4 Signals
PID-6189-INPUTSIGNALS v5
Table 582: SINGLECMD Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block single command function
PID-6189-OUTPUTSIGNALS v5
Table 583: SINGLECMD Output signals
Name Type Description
OUT1 BOOLEAN Single command output 1
OUT2 BOOLEAN Single command output 2
OUT3 BOOLEAN Single command output 3
OUT4 BOOLEAN Single command output 4
OUT5 BOOLEAN Single command output 5
OUT6 BOOLEAN Single command output 6
OUT7 BOOLEAN Single command output 7
OUT8 BOOLEAN Single command output 8
OUT9 BOOLEAN Single command output 9
OUT10 BOOLEAN Single command output 10
OUT11 BOOLEAN Single command output 11
OUT12 BOOLEAN Single command output 12
OUT13 BOOLEAN Single command output 13
OUT14 BOOLEAN Single command output 14
OUT15 BOOLEAN Single command output 15
OUT16 BOOLEAN Single command output 16
14.10.5 Settings
PID-6189-SETTINGS v5
Table 584: SINGLECMD Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Steady
Pulsed
- - Disabled Operation Disabled/Enabled
14.10.6 Operation principle
M12447-3 v3
Single command, 16 signals (SINGLECMD) function has 16 binary output signals. The outputs can
be individually controlled from a substation automation system or from the local HMI. Each output
signal can be given a name with a maximum of 13 characters in PCM600.