Function IEC 61850 Logical device Logical nodes in
Ver.5.0 FP1
Logical nodes in
Ver.5.0 or older
Fault locator SCEFRFLO LD0 SCEFRFLO
SCEFZLIN
SCEF2ZLIN
SCEF3ZLIN
FLORFRC
SCEFRFLO
FLOMSTA
Phase power directional function DPSRDIR LD0 DPSRDIR
Power quality
Current total demand distortion CMHAI LD0 CMHAI CMHAI
Voltage total harmonic distortion VMHAI LD0 VMHAI VMHAI
Voltage variation PHQVVR LD0 PHQVVR
PH2QVVR
PH3QVVR
QVVRQRC
QVV2RQRC
QVV3RQRC
PHQVVR
PH2QVVR
PH3QVVR
QVVMSTA
QVV2MSTA
QVV3MSTA
Voltage unbalance
VSQVUB LD0
VSQVUB
QVU1RQRC
QVU2RQRC
QVU3RQRC
Control
Local/remote control function block Control CTRL LLN0
LPHD1
LLN0
LPHD1
Circuit breaker control CBXCBR CTRL CBCSWI
CBCILO
CBXCBR
CBCSWI
CBCILO
CBXCBR
Disconnector control
DCXSWI CTRL DCCSWI
DCCILO
DCXSWI
DCCSWI
DCCILO
DCXSWI
Disconnector position indication
DCSXSWI CTRL DCSXSWI DCSXSWI
Earthing switch indication ESSXSWI CTRL ESSXSWI ESSXSWI
Autoreclosing DARREC LD0 DARREC DARREC
Synchronism and energizing check SECRSYN LD0 SECRSYN SECRSYN
Automatic transfer switch ATSABTC LD0 ATSABTC ATSABTC
Condition monitoring
Circuit-breaker condition monitoring SSCBR1 LD0 SSCBR1
SPH1SCBR
SPH2SCBR
SPH3SCBR
SSOPM
SSIMG
SSCBR1
Trip circuit supervision TCSSCBR LD0 TCSSCBR TCSSCBR
Current circuit supervision CCSPVC LD0 CCSPVC CCRDIF
Fuse failure supervision SEQSPVC LD0 SEQSPVC SEQRFUF
Runtime counter for machines and devices MDSOPT LD0 MDSOPT MDSOPT
Voltage presence PHSVPR LD0 PHSVPR PHSVPR
Measurement