5.5.2 Fault Record tool interface
GUID-F27BFF9C-DB85-430C-8B80-5ECE3A4E3D35 V1 EN
Figure 59: Fault record tool
Table 6: Available actions on the user interface
Action
Description
Read Clicking the Read button reads all available fault records from the protection relay
into the tool. User has the option to read 1 fault record, 20 fault records or all fault
records. The Read button opens up a progress bar to indicate an ongoing read
operation.
Click the Cancel button on the Read progress bar to cancel the read operation. On
operation completion, the available fault records are shown in the record grid.
Click the + icon to expand and view record details.
Save
Click Save to save the fault records on the local machine as .txt file.
Clear Record can be cleared from either the Fault record tool or the protection relay or
both. Before deleting the records, a confirmation dialog box is shown.
Close Clicking the Close button closes this instance of the Fault Record tool. Any open
instance is finally closed when the whole PCM600 is closed.
File File menu for Save and Exit actions.
Edit Copy All in the Edit menu allows to copy all the fault records which can then be
pasted to a word processor and saved on the local machine without having to save
the records as a .txt file.
Additionally the user can select any particular fault record and right-click to copy the
selected record.
1MRS757810 C Section 5
Protection and control engineering
REC615 and RER615 85
Engineering Manual