All functions listed in Obsolete Functions and Hardwares.
All parameters for which the migration failed. See the migration report for
failed parameters.
Parameters of the DNP3 related functions that are reset to default values in
migration. Restore the original parameters.
Note that some functions may have new settings.
8.5.3 Reengineering in the IEC 61850 Configuration tool
I CM automatically updates the names according to the new version names. Migration
report describes the details of the changes in dataset entries.
For the function block names in IEC 61850 Edition 1 and Edition 2,
see Table 11.
8.5.4 Reengineering in the Communication Management Tool
8.5.4.1 Checking and updating DNP3 points
If DNP3 is used, the migrated DNP3 point list should for most part correspond to the
configuration made in the old IED.
1. Check the point list and verify that all the point types correspond to the old
configuration and DNP3 master.
Analog input objects
Binary input objects
Binary output objects
Counter objects
Double bit indication objects
Analog output objects
2. If some points have different point addresses or other mapping attributes, adjust
them in the Communication Management tool.
3. Add the possible missing points in the migrated configuration by taking them
back to use in the Communication Management tool.
8.5.4.2 Checking and updating Modbus points
If Modbus is used, the migrated Modbus point list should for most part correspond to
the configuration made in the old IED.
Section 8 1MRS757810 C
Configuration migration
136 REC615 and RER615
Engineering Manual