When a changed configuration is written to the protection relay, the horizontal
communication configuration needs to be updated.
GUID-B0BAFCF2-2396-4DC1-883D-1E9FB1EC22CF V1 EN
Figure 90: Updating the communication configuration in the IED with the
configuration made in PCM600
1. Select which configuration part to include in writing.
• Select GOOSE to update the GOOSE configuration part in the IED.
• Select Process bus (IEC 61850-9-2) to update the IEC 61850-9-2
configuration part in the IED.
2. Select whether or not to update the configuration.
• Click Continue to update the selected communication configuration
part(s) in the IED. The options can be left unselected. In this case, other
parts of the configuration are updated.
• Click Cancel to cancel the whole writing operation.
Section 7 1MRS757810 C
IEC 61850 communication engineering
126 REC615 and RER615
Engineering Manual