Working in the offline mode has an advantage compared to online mode in that the
preparation for the configuration can be started even though the protection relay is not
available.
1. In the Plant Structure view, right-click the bay, point to New, point to the IED
application area such as Remote Monitoring and Control IEDs or Recloser
Protection and Control IEDs.
Alternatively, drag an IED from the Object Types view to the
bay level.
2. On the Configuration mode selection page, select Offline Configuration and
click Next.
Setting up an IED in the offline mode is similar as in the online mode; however,
with the offline mode it is not necessary to type the correct IP address in the
Communication port and IP address dialog box.
GUID-3629E365-57F1-41B8-A16F-811F5D218AD2 V3 EN
Figure 27: PCM600: Configuration Mode Selection Wizard
3. On the Order Code selection page, select the correct order codes and click
Next.
Ensure that the order code is correct. PCM600 verifies later that
the order code matches with the relay. If the order code digits
related to the configuration, I/O or version do not match with the
Section 4 1MRS757810 C
Setting up a project
50 REC615 and RER615
Engineering Manual