Table 15: Secondary IP address parameters
Parameter Options Description
Configuration/Communica-
tion/Ethernet/Network 2 ad-
dress/ Enable
False (default) Network 2 disabled
TRUE Network 2 enabled
Configuration/Communica-
tion/Ethernet/Network 2 ad-
dress/IP address
0.0.0.0 IP address for Network 2
Configuration/Communica-
tion/Ethernet/Network 2 ad-
dress/IP address
0.0.0.0 Subnet address for Network 2
Configuration/Communica-
tion/Ethernet/Network 2 ad-
dress/MAC address
xx-xx-xx-xx-xx-xx MAC address for Network 2
The IP address for Network 2 is disabled by default settings, and all Ethernet
ports are assigned to the same IP address used in the Network 1 address menu
Configuration> Communication> Ethernet> Network 1. If Network 2 is taken
into use by the setting Enable="True" (requires reboot), the interlink port X3 of the
COM module is assigned to this second network, using the IP address and subnet
parameters in the Network 2 address menu Configuration> Communication>
Ethernet> Network 2 address.
If the Network 2 interface is enabled, PTP time synchronization and SMV/
GOOSE multicast are disabled for that port.
1MRS759118 D Commissioning
REX640
Operation Manual
117