ABB | SACE Emax 2
Ekip Touch - Measurements
1 - Standard Measurements
113 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Ekip Touch - Measurements
1 - Standard Measurements
List
The Standard measurements are:
Parameter Description Page
Instantaneous currents
Phase current and earth fault measurements in
real time
113
Events
List of events, status changes, alarms, recorded
by the Trip unit
113
Trip
List of current protection trips (TRIP) 113
Min-Max
measurements
History of minimum and maximum currents,
recorded at a settable interval
115
Maintenance
CB status: contact wear and last maintenance 116
Operation counters
Number of mechanical and electrical operations 116
Instantaneous currents
The instantaneous currents, available in the
Measurements
pages, are real time measurements of the
phase and earth fault currents expressed in root mean square value; the monitor time and performance
depend on the rated current defined by the Rating plug (In):
Measurement
Monitor time
(min-max)
Normal operating
range
Accuracy of value
read
(1)
Phase currents
(4)
0,004 ÷ 64 In 0,2 ÷ 1,2 In 1%
(3)
Internal earth fault current
(2)
0,08 ÷ 64 In 0,2 ÷ 1,2 In 2 %
(3)
External earth fault current
(2) (4)
0,08 ÷ 4 In 0,2 ÷ 1,2 In 2 %
Residual current
(2) (5)
2 ÷ 32 A 5 %
(1)
the accuracies refer to normal operating ranges, as established by IEC 61557-12
(2)
available with LSIG versions
(3)
accuracies based on Ekip Touch without Class 1 Power & Energy Metering package; if the Class 1
Power & Energy Metering package is present and for all other trip unit models, check the indicated
performance values from page 120
(4)
the higher phase currents are also available in the Histograms, Measuring instruments and
Measurement summary pages
(5)
available by activating the presence of toroid S.G.R or Rc
Special representations
Type of measure-
ment
Measurement < min
value
Measurement > max
value
“_ _ _” displayed:
(not available) due to
Internal earth fault and
phase currents
. . . . [64 In]
(1)
Sensors disconnected
External earth fault
current
. . . . > [4 In toroid]
Toroid not activated
and/or disconnected
Residual current . . . . > 32 A
Toroid not activated
and/or disconnected