EasyManua.ls Logo

ABB SACE Emax 2 Series - List of Alarms and Signals

ABB SACE Emax 2 Series
302 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB | SACE Emax 2ABB | SACE Emax 2
32 | © 2023 ABB | 1SDH001330R1002 - ECN000297030 Ekip Dip
5 - List of alarms and signals
LED view
Ekip Dip continuously monitors its own operating condition and that of all the devices to which it is connected. All the signals are available
with the front LEDs. The protection LEDs provide information with various combinations of lighting and flashing, while the power-on LED, as
described on page 22, indicates the power-on conditions of the trip unit.
NOTE:
the number of LEDs depends on the version of Ekip Dip (LI, LSI, LSIG).
Summary table of LED signals
The following table summarises the signals available with the protection LEDs and the operations to be carried out in response to alarms or fault
conditions signalled.
Type of Information
Slow flashing
(0.5Hz)
Fast flashing (2 Hz) On and fixed
2 flashes
every 2 s
3
flashes
every
3 s
4
flashes
every
4 s
HELP
Colour and LED All R G
All
R+G
All R
R
(single)
G
All
R+G
All R
R
(single)
G All R G G G
Internal configuration
error
(5)
.
x x x A
Trip coil disconnected
or trip command failed
x B
Current sensors
disconnected
x B
Rating Plug error X B+E
Protection delay x C
Temperature alarm
(1)
x C
Pre-alarm L x C
Trip
(2)
x C
Hardware Trip
(3)
x x B
Installation error x E
Parameter error x D
Circuit-breaker state
not defined or in error
x B
Error on Local Bus x F
Maintenance alarm x F
Software
incompatibility
x x G
Low battery (during
self-test)
(4)
x H
(1)
The temperature alarm is signalled by lighting of the protection L and I red LEDs.
(2)
The last trip can also be displayed with trip unit off, by pressing the iTest key.
(3)
The Hardware Trip is signalled by lighting of the pre-alarm L yellow LED and the protection I red led.
(4)
Five flashes when self-test is started up
(5)
Error present with one of the three flashing options displayed alongside.
Key to LED colours
The above table lists the colors of the LEDs, to be interpreted as follows:
R = red LED (alarm LED L, S, I, G).
G = yellow LED (pre-alarm LED L).
NOTE:
for further details refer to the table listing the components of the interface, available on page
21.
Continued on the next page

Table of Contents

Other manuals for ABB SACE Emax 2 Series

Related product manuals