ABB | SACE Emax 2
Other electronic accessories
10 -
Testing and Programming
259 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
10 - Testing and Programming
Ekip TT
Ekip TT
is a supply accessory and is useful for powering Ekip Touch in the absence of auxiliary power
supply; the unit allows:
Ekip Touch to be supplied and the tripped protection to be displayed, in the event of a TRIP and
absence of auxiliary voltage
the protections and certain parameters to be set before installation in the system
IMPORTANT:
Ekip TT can also be connected to Ekip Touch when in service.
Ekip TT only supplies the Trip unit: the presence of an auxiliary supply is required in order
to set and display the information about the electronic accessories
Ekip TT is connected to the service connector of Ekip Touch by means of the supplied cable.
To switch on the module, set the side switch to the ON position and check the status of the led:
if green, proceed with the required reading and configuring operations
if red, replace the batteries of the device (three 1.5 V AA batteries)
Further details are available in ABB Library, especially in document 1SDH001000r0519