ABB | SACE Emax 2
Mechanical accessories
2 - Mechanical safety accessories
189 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
DLP
(1)
: door opening lock
with the circuit-breaker in
connected/test position
The DLP lock prevents the switchgear door from being opened when the moving part of the circuit-
breaker is in the connected or test position.
It can be installed alternatively on the right side or the left side of the fixed part.
NOTE:
The DLP lock is used as an alternative to the mechanical interlock.
DLP for E2.2 - E4.2 - E6.2
(1)
Not available for E1.2
Information on the assembly is available on the website http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet 1SDH001000r0709.
DLR
(1)
: lock on racking-in/
racking-out of the moving part
with the door open
The DLR lock prevents the moving part from being racked in/out from the fixed part when the switchgear
door is open.
It is available on request on all fixed parts.
DLR for E2.2 - E4.2 - E6.2
(1)
Not available for E1.2
Information on the assembly is available on the website http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet 1SDH001000r0725.
Fail safe
The fail safe is a device that prevents the removal of the mobile part of a withdrawable circuit-breaker
from the fixed part if the springs are charged.
It is always supplied with UL circuit-breakers.
IMPORTANT:
The fail safe device makes undervoltage coil YU unavailable.
It is, however, possible not to install the fail safe device, in which case the undervoltage
coil YU must be used.
Information on the assembly is available on the website http://www.abb.com/abblibrary/
DownloadCenter/, in particular for E1.2 in the kit sheets
1SDH000999r0708 for the Fail Safe, movable part
1SDH000999r0711 for the Fail Safe, fixed part
and for E2.2-E4.2-E6.2 in the kit sheet 1SDH001400r0821.