ABB | SACE Emax 2
Electrical accessories
1 - Electrical control accessories
194 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Continued from the previous page
The tables listing the available voltages and the electrical characteristics are provided below:
Available voltages (Un)
24 V AC/DC
30 V AC/DC
48 V AC/DC
60 V AC/DC
110…120 V AC/DC
220…240 V AC/DC
240...250 V AC/DC
277 V AC/DC
380…400 V AC
415…440 V AC
480…500 V AC
General characteristics YU
Inrush power (Ps) 300 VA/W
Continuous power (Pc) 3.5 VA/W
Opening time 50 ms
YU: Connections
More details are available in the website http://www.abb.com/abblibrary/DownloadCenter/, which also
includes the entire circuit diagram 1SDM000091r0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/
DownloadCenter/, in particular for E1.2 in the kit sheet 1SDH000999r0504 and for E2.2-E4.2-E6.2 in the
kit sheet 1SDH001000r0504.
YR: Remote resetting coil
The remote resetting coil deactivates the lock at the closing of the circuit-breaker, generated by the
opening of the circuit-breaker caused by tripping of the Ekip protection trip unit.
R2
R1
YR
YR for E1.2
R2
R1
YR
YR for E2.2 - E4.2 - E6.2
The tables listing the available voltages and the electrical characteristics are provided below:
Available voltages (Un)
24 V AC
(1)
24 V DC
(1)
110 V AC
(1)
110 V DC
(1) (2)
220 V AC
(1)
220 V DC
(1) (2)
General characteristics
Operating limits 90...110 %Un
(1)
The coil must be activated by a pulse lasting at least 20ms.
(2)
The coil must be activated by a pulse lasting max 50ms.
YR: Connections
More details are available in the website http://www.abb.com/abblibrary/DownloadCenter/, which also
includes the entire circuit diagram 1SDM000091r0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/
DownloadCenter/, in particular for E1.2 in the kit sheet 1SDH000999r0606 and for E2.2-E4.2-E6.2 in the
kit sheet 1SDH001000r0606.