ABB | SACE Emax 2
Internal electronic accessories
3 - Ekip Signalling 4K
210 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Continued from the previous page
Parameter Description Default
min
Activation
Time
(2)
If Self-latching = Off, defines the minimum activation time of the output
in the presence of rapid Sources:
• Source duration < Min activ. time = the output remains activated for the
duration of the Min activ. time
• Source duration < Min activ. time = the output remains activated for as
long as the Source persists
Choose between: 0 ms, 100 ms, 200 ms
0 ms
(1)
deactivate the self-latchings of the outputs used for Power Controller if the module is used for the
Power Controller function
(2)
the Pulse Mode option will be available as well as those described if the module is used for the
Power Controller function. If selected, the output is maintained active for a fixed time pertaining to
the function itself, regardless of whether the event that activated it persists or not.
Input parameters
All the inputs enable the following parameters to be configured:
Parameter Description Default
Polarity
Defines whether the state of the input is ON when the contacts
are open (Active open) or short-circuited (Active Closed)
Active closed
Delay
Minimum activation and deactivation time of an input enabling
a change of state to be recognized by the trip unit; the Delay is
given in seconds and can be set within a range between 0 s and
100 s, in 0.01 s steps.
NOTES:
•
the trip unit will not detect a change of state if it is
present for less than the set Delay
•
if Delay = 0 s, the change of state must still be more than
300 mS
0.1 s
About
The
About
-
Modules
menu contains the specific area for
Ekip Signalling 4K
, in which the states of the
inputs (
On
/
Off
) and outputs (
Open
/
Closed
) are present.
Test
The dedicated area in the
Test
menu is activated if
Ekip Signalling 4K
is detected correctly by the trip unit.
For details of the test characteristics, please consult page 137.
Commands and functions
If Self-latching = On, the activated output contacts can be reset with:
• automatic command
RESET signaling
, which can be programmed in the
Settings
-
Modules
-
Functions
menu of Ekip Touch or via Ekip Connect (see page xx)
• manual command via the service connector (via Ekip Connect) or via system bus communication